Programming manual
Monitoring the control panel 95
21-10
Monitoring wireless devices
Via softwareClick on the Monitoring button on the menu bar, then go to the “Wireless devices” section.
After clicking-on the Update button, this section shows a list of all the wireless devices
connected to the control panel.
The monitoring-operation provides the following feedback for each device:
• an index of the reception quality of the wireless signal
• the percentage of the battery charge
The colour of the values shown also indicates the level of both the signal index and the charge
(red-orange-green).
21-11
Walk test
This section provides a quick and easy way of testing all the configured inputs.
After initializing the Walk test, all the operator need to do is walk through the protected
partitions and then check the detection capacity of the inputs via the system keypad or Prime/
STUDIO software application.
Via keypad
Type-in Code
(Installer),
PROGRAMMING Walk test
Access to this section opens the full list of configured zones on the keypad display.
As these input zones are violated by the operator carrying out the walk test, they will be
cleared from the list and the keypad will emit a long beep.
You can consider the outcome of test positive when there are no zones left on the list.
Via softwareClick on the Monitoring button on the menu bar, then go to the “Programming, Sounder/
flashers” section.
The list of zones and the Start Walk test button will be shown.
Once the test starts, the operator can walk through the entire area protected by the system
and verify the correctness of the detection capacity of the inputs by means of the information
reported in this section, marking the violated areas with a red dot and the time of the
violation.
The Print Walk test button allows the so0ftware to print the test results.