Programming manual
Programming events 71
EXAMPLES
If you want to generate an alarm (i.e. activate sounder/flashers and calls) when only two PIRs (DET1
and DET2) go into alarm status within a pre-set time.
T0000; timer 1 will activate when the “Zone alarm DET1” Start event activates for 30 seconds
T0001; timer 2 will activate when the start event of the “Zone alarm DET2” S activates for 30 seconds
Both conditions must occur together (AND)
T0000 AND T0001
Therefore, it is necessary to program the activation of the sounder/flasher and telephone calls for the event
organized in this way.
If the programmable event activates an on-BUS sounder/flasher, associate its deactivation with an event.
If you wish to activate an output for 40 seconds when key 17 is used to arm partition 1, and to disarm
and the same output when the partition disarms.
T0000; associate timer 1 with the activation of the Start event of key 17 recognition
T0000; timer 1 with a 40 second timeout, “timer active with delay” option enabled
T0000; associate timer 1 with the restoral of the reset event of partition 1
Programmable event 1 must be programmed as:
T0000
Select the output you want to activate in concurrence with the programmable event
If the programmable event activates an on-BUS sounder/flasher, associate its deactivation with an event.
If you wish to receive a phone call when a zone q, which belongs to partitions 1 and 2, is violated and
one of the two partitions is armed
The automation zone q always generates the zone alarm event (even when the partitions are disarmed).
However, the programmable event will occur only when the zone q is in alarm status and at least one of
the two partitions is armed.
Configure zone q as “automation” belonging to partitions 1 and 2
Remove all the outputs and phone calls associated with the “Alarm zone q” event
The programmable event must be programmed as “Alarm zone q” AND (“Partition 1 armed in away mode”
OR “Partition 2 armed in away mode”):
E0010 AND ( E7215 OR E7216 )
Associate the programmable event with the phone call you wish to receive
If you wish to activate a phone call after 3 consecutive wrong code entries (with a maximum of 120
seconds between each entry).
C0000; counter 1 will activate on activation of the “False code” Start event, with a count of 3, 120 second
autoreset time
The programmable event must be programmed as:
C0000
Associate the programmable event with the phone call you wish to receive
If you wish to activate a phone call and output when at least two detectors out of 5 go into alarm status.
The programmable event must be programmed as (“Alarm zone 1” + “Alarm zone 2” + “Alarm zone 3” +
Alarm zone 4” + “Alarm zone 5”)>=2
( E0000 + E0001 + E0002 + E0003 + E0004 ) >= V0002
Associate the programmable event with the phone call you wish to receive and the output you wish to
activate.