Goodrive200 inverters Function codes
100
Function
code
Name
Detailed instruction of parameters
Default
value
DEC time
3
Depend
on
model
ACC time
4
Depend
on
model
DEC time
4
Depend
on
model
This parameter is used to define the reference
frequency during jogging.
Setting range: 0.00Hz ~P00.03
(the Max. frequency)
5.00Hz
The jogging ACC time means the time needed if
the inverter runs from 0Hz to the Max.
Frequency.
The jogging DEC time means the time needed if
the inverter goes from the Max. Frequency
(P0.03) to 0Hz.
Setting range:0.0~3600.0s
Depend
on
model
Jumping
frequency
1
When the set frequency is in the range of
jumping frequency, the inverter will run at the
edge of the jumping frequency.
The inverter can avoid the mechanical resonance
point by setting the jumping frequency. The
inverter can set three jumping frequency. But this
function will be invalid if all jumping points are 0.
Jumping
frequency
range 1
Jumping
frequency
2
0.00Hz