Maintenance and hardware diagnostics
218
380V charging illustration of the driven device
9.4.2 Change electrolytic capacitors
Read and follow the instructions in chapter Safety Precautions.
Ignoring the instructions may cause physical injury or death, or
damage to the equipment.
Change electrolytic capacitors if the working hours of electrolytic capacitors in the inverter
are above 35000. Please contact with the local INVT offices or dial our national service
hotline (400-700-9997) for detailed operation.
9.5 Power cable
Read and follow the instructions in chapter Safety Precautions.
Ignoring the instructions may cause physical injury or death, or
damage to the equipment.
1. Stop the drive and disconnect it from the power line. Wait for at least the time designated
on the inverter.
2. Check the tightness of the power cable connections.
3. Restore power.