Goodrive200 inverters Function codes
119
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
ACC/DEC
time
Functio
n code
Binary bit
Step
ACC/DE
C 0
ACC/DE
C 1
ACC/DE
C 2
ACC/DE
C 3
P10.34
BIT1
BIT0
0 00 01 10 11
BIT3
BIT2
1 00 01 10 11
BIT5
BIT4
2 00 01 10 11
BIT7
BIT6
3 00 01 10 11
BIT9
BIT8
4 00 01 10 11
BIT11
BIT10
5 00 01 10 11
BIT13
BIT12
6 00 01 10 11
BIT15
BIT14
7 00 01 10 11
P10.35
BIT1
BIT0
8 00 01 10 11
BIT3
BIT2
9 00 01 10 11
BIT5
BIT4
10 00 01 10 11
BIT7
BIT6
11 00 01 10 11
BIT9
BIT8
12 00 01 10 11
BIT11
BIT10
13 00 01 10 11
BIT13
BIT12
14 00 01 10 11
BIT15
BIT14
15 00 01 10 11
After the users select the corresponding
ACC/DEC time, the combined 16 binary bits will
change into decimal bit, and then set the
corresponding function codes.
Setting range: 0x0000~0xFFFF
P10.35
Simple
PLC 8~15
step
ACC/DEC
time
0x0000
P10.36
PLC
restart
0: Restart from the first step; stop during running
(cause by the stop command, fault or power
loss), run from the first step after restart.
1: Continue to run from the stop frequency; stop
during running(cause by stop command and
fault), the inverter will record the running time
automatically, enter into the step after restart and
keep the remaining running at the setting
0