Goodrive200 inverters Function codes
120
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
frequency.
P10.37
Multi-step
time unit
0: Seconds; the running time of all steps is
counted by second
1: Minutes; the running time of all steps is
counted by minute
0
P11 Group Protective parameters
P11.00
P
hase loss
protection
0x00~0x11
LED ones:
0: Input phase loss protection disable
1: Input phase loss protection enable
LED tens:
0: Input phase loss protection disable
1: Input phase loss protection enable
Note: The value for inverters of 15kW and
belowis default as 10
11
P11.01
Sudden
power loss
frequency-
decreasing
0: Enable
1: Disable
0
P11.02
Frequenc
y
decreasing
ratio of
sudden
power loss
Setting range: 0.00Hz/s~P00.03
(the Max. frequency)
After the power loss of the grid, the bus voltage
drops to the sudden frequency-decreasing point,
the inverter begin to decrease the running
frequency at P11.02, to make the inverter
generate power again. The returning power can
maintain the bus voltage to ensure a rated
running of the inverter until the recovery of
power.
Voltage degree 220V
380V
660V
Frequency-decrea 260V
460V
800V
10.00
Hz/s