Goodrive200 inverters Function codes
121
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
sing point at
sudden power loss
Note:
1. Adjust the parameter properly to avoid the
stopping caused by inverter protection during the
switching of the grid.
2. Disable input phase loss protection to enable
this function.
P11.03
Overvoltag
e stall
protection
0:Disable
1:Enable
1
P11.04
Protection
voltage at
overvoltag
e stall
120~150%(standard bus voltage) (380V) 136%
120~150%(standard bus voltage) (220V) 120%
P11.05
Current
limit action
selection
The actual increasing ratio is less than the ratio
of output frequency because of the big load
during ACC running. It is necessary to take
measures to avoid overcurrent fault and the
inverter trips.
During the running of the inverter, this function
will detect the output current and compare it with
the limit defined in P11.06. If it exceeds the level,
the inverter will run at stable frequency in ACC
running, or the inverter will derate to run during
the constant running. If it exceeds the level
01
P11.06
Automatic
current
limit
G:
160.0%
P:
120.0%
P11.07
The
decreasing
ratio during
10.00
Hz/s