7.12 Digital output
Goodrive200 series inverters have 2 relay output terminals and 1 open-collector output terminal
and 1 high speed pulse output terminal in the standard configuration. All functions of the digital
input terminals are programmable by the function codes. Open collector pole output can be
selected into high speed pulse input terminal or common switch input terminal by function code.
The below table is the option of the four function parameters and selecting the repeated output
terminal function is allowed.
Set value
Function Instructions
0 Invalid The output terminal has no function.
1 Running
Output ON signal when the inverter is running and
there is frequency output.
2 Forward running
Output ON signal when the inverter is running
forward and there is frequency output.
3 Reverse running
Output ON signal when the inverter is running
reverse and there is frequency output.
4 Jogging
Output ON signal when the inverter is jogging and
there is frequency output.
5 Inverter fault Output ON signal when the inverter is in fault
6 FDT1
Please refer to P08.32 and P08.33 for detailed
information.
7 FDT2
Please refer to P08.34 and P08.35 for detailed
information.
8 Frequency arrival Please refer to P08.36 for detailed information.
9 Zero-speed running
Output ON signal when the output frequency and
reference frequency of the inverter is 0 at the same