EasyManuals Logo
Home>INVT>Inverter>GD200-037G/045P-4

INVT GD200-037G/045P-4 User Manual

INVT GD200-037G/045P-4
266 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #137 background imageLoading...
Page #137 background image
Goodrive200 inverters Basic operation instruction
136
issue.
Besides P00.01 and P00.02, terminal command setting can also used to set the running command
channel.
Current running
command
channel
P00.01
Multi-function
terminal 36
Shifting the
command to keypad
Multi-function
terminal 37
Shifting the
command to
communication
Multi-function
terminal 38
Shifting the
command to
communication
Keypad running
command channel
/
Terminal running
command channel
Communication
running command
channel
Terminal running
command channel
Keypad running
command channel
/
Communication
running command
channel
Communication
running command
channel
Keypad running
command channel
Terminal running
command channel
/
Note: / means the multi-function terminal is invalid on the current reference channel.
Relative parameters table:
Function
code
Name Detailed instruction of parameters
Default
value
P00.00 Speed control mode
1: SVC
2: SVPWM control (applying to AM)
2
P00.01 Run command channel
0:Keypad running command channel
(LED off)
1:Terminal running command channel
(LED flickering)
2:Communication running command
channel (LED on)
0
P00.02
Communication running
commands
0:MODBUS communication channel
1~ 3:Reserved
0
P00.18
Function
restore parameter
0:No operation
1:Restore the default value
2:Clear fault records
0

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT GD200-037G/045P-4 and is the answer not in the manual?

INVT GD200-037G/045P-4 Specifications

General IconGeneral
BrandINVT
ModelGD200-037G/045P-4
CategoryInverter
LanguageEnglish

Related product manuals