Goodrive200 inverters Basic operation instruction
136
issue.
Besides P00.01 and P00.02, terminal command setting can also used to set the running command
channel.
Current running
command
channel
P00.01
Multi-function
terminal 36
Shifting the
command to keypad
Multi-function
terminal 37
Shifting the
command to
communication
Multi-function
terminal 38
Shifting the
command to
communication
Keypad running
command channel
/
Terminal running
command channel
Communication
running command
channel
Terminal running
command channel
Keypad running
command channel
/
Communication
running command
channel
Communication
running command
channel
Keypad running
command channel
Terminal running
command channel
/
Note: “/” means the multi-function terminal is invalid on the current reference channel.
Relative parameters table:
Function
code
Name Detailed instruction of parameters
Default
value
P00.00 Speed control mode
1: SVC
2: SVPWM control (applying to AM)
2
P00.01 Run command channel
0:Keypad running command channel
(LED off)
1:Terminal running command channel
(LED flickering)
2:Communication running command
channel (LED on)
0
P00.02
Communication running
commands
0:MODBUS communication channel
1~ 3:Reserved
0
P00.18
Function
restore parameter
0:No operation
1:Restore the default value
2:Clear fault records
0