Goodrive200 inverters Basic operation instruction
181
PLC finishes a circle (or a step).
Relative parameters list:
Function
code
Name Detailed instruction of parameters
Default
value
P10.00 Simple PLC
0:Stop after running once
1:Run at the final value after running
once
2:Cycle running
0
P10.01 Simple PLC memory
0:Power loss without memory
1:Power loss memory
0
P10.02 Multi-step speed 0 -100.0~100.0% 0.0%
P10.03
T
he running time of step
0
0.0~6553.5s(min) 0.0s
P10.04 Multi-step speed 1 -100.0~100.0% 0.0%
P10.05 T
he running time of step 1
0.0~6553.5s(min) 0.0s
P10.06 Multi-step speed 2 -100.0~100.0% 0.0%
P10.07 T
he running time of step 2
0.0~6553.5smin 0.0s
P10.08 Multi-step speed 3 -100.0~100.0% 0.0%
P10.09 T
he running time of step 3
0.0~6553.5s(min) 0.0s