Goodrive200 inverters Function codes
122
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
current
limit
continuously, the output frequency will keep on
decreasing to the lower limit. If the output current
is detected to be lower than the limit level, the
inverter will accelerate to run.
Setting range of P11.05:
0x00~0x11
LED ones:current limit
0:Invalid
1:Always invalid
LED tens:overload alarm
0:Valid
1: Invalid
Setting range of P11.06: 50.0~200.0%
Setting range of P11.07: 0.00~50.00Hz/s
P11.08
Overload
pre-alarm
of the
motor/inver
ter
The output current of the inverter or the motor is
above P11.09 and the lasting time is beyond
P11.10, overload pre-alarm will be output.
0x000
P11.09
Overload
pre-alarm
test level
G:
150%
P:
120%
P11.10
Overload
pre-alarm
1.0s