Goodrive200 inverters Function codes
123
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
detection
time
Setting range of P11.08:
Enable and define the overload pre-alarm of the
inverter or the motor.
Setting range: 0x000~0x131
LED ones:
0:Overload pre-alarm of the motor, comply with
the rated current of the motor
1:Overload pre-alarm of the inverter, comply with
the rated current of the inverter
LED tens:
0:The inverter continues to work after underload
pre-alarm
1:The inverter continues to work after underload
pre-alarm and the inverter stops running after
overload fault
2: The inverter continues to work after overload
pre-alarm and the inverter stops running after
underload fault
3. The inverter stops when overloading or
underloading.
LED hundreds :
0:Detection all the time
1:Detection in constant running
Setting range of P11.09: P11.11~200%
Setting range of P11.10: 0.1~3600.0s
P11.11
Detection
level of the
underload
pre-alarm
If the inverter current or the output current is
lower than P11.11, and its lasting time is beyond
P11.12, the inverter will output underload
pre-alarm.
Setting range of P11.11: 0~P11.09
Setting range of P11.12: 0.1~3600.0s
50%
P11.12
Detection
time of the
1.0s