Goodrive200 inverters Product overview
14
Function Specification
Running
control
feature
Digital setting, analog setting, pulse frequency
setting, multi-step speed running setting, simple
PLC setting, PID setting, MODBUS communication
setting.
Shift between the set combination and set channel.
Auto voltage
adjustment
Keep a stable voltage automatically when the grid
voltage transients
Fault protection
Provide over 30 fault protection functions:
overcurrent, overvoltage, undervoltage, overheating,
phase loss and overload, etc.
Speed tracking
Restart the rotating motor smoothly
Note: This function is available for the inverters of
4kW and above 4kW.
Peripheral
interface
Terminal analog input
resolution
≤ 20mV
Terminal switch input
resolution
≤ 2ms
Analog input
2 channels (AI1, AI2) 0~10V/0~20mA and 1 channel
(AI3) -10~10V
Analog output 2 channels (AO1, AO2) 0~10V /0~20mA
Digital input
8 channels common input, the Max. frequency:
1kHz, internal impedance: 3.3kΩ;
1 channel high speed input, the Max. frequency:
50kHz
Digital output
1 channel high speed pulse output, the Max.
frequency: 50kHz;
1 channel Y terminal open collector pole output
Relay output
2 channels programmable relay output
RO1A NO, RO1B NC, RO1C common terminal
RO2A NO, RO2B NC, RO2C common terminal
Contactor capability: 3A/AC250V,1A/DC30V
Others
Wall, flange and floor mountable