Goodrive200 inverters Basic operation instruction
162
Relative parameters list:
Function
code
Name Detailed instruction of parameters
Default
value
P05.00 HDI input selection
0: HDI is high pulse input
1: HDI is switch input
0
P05.32 Lower limit of AI1 0.00V~P05.25 0.00V
P05.33
Corresponding setting of
the lower limit of AI1
-100.0%~100.0% 0.0%
P05.34 Upper limit of AI1 P05.23~10.00V 10.00V
P05.35
Corresponding setting of
the upper limit of AI1
-100.0%~100.0% 100.0%
P05.36 AI1 input filter time 0.000s~10.000s 0.100s
P05.37
Lower limit of
AI2
0.00V~P05.30 0.00V
P05.38
Corresponding setting of
the lower limit of AI2
-100.0%~100.0% 0.0%
P05.39 Upper limit of AI2 P05.28~10.00V 10.00V
P05.40 Corresponding setting of
-100.0%~100.0% 100.0%