Goodrive200 inverters
Appendix C
255
escape from the breaker enclosure in case of a short-circuit. To ensure
safe use, special attention must be paid to the installation and
placement of the breakers. Follow the manufacturer’s instructions.
Inverter Breaker (A) Fuse (A)
Rated current of the
reactor (A)
GD200-1R5G-4 10 16 12
GD200-2R2G-4 16 16 12
GD200-004G/5R5P-4
16 25 12
GD200-5R5G/7R5P-4
25 32 25
GD200-7R5G/011P-4
40 40 25
GD200-011G/015P-4
50 50 40
GD200-015G/018P-4
63 63 40
GD200-018G/022P-4
63 80 50
GD200-022G/030P-4
80 100 65
GD200-030G/037P-4
100 125 80
GD200-037G/045P-4
125 160 95
GD200-045G/055P-4
160 160 115
GD200-055G/075P-4
160 200 150
GD200-075G/090P-4
250 250 185
GD200-090G/110P-4
250 315 225
GD200-110G/132P-4
315 315 265
GD200-132G/160P-4
350 400 330
GD200-160G/185P-4
400 500 400
GD200-185G/200P-4
500 630 500
GD200-200G/220P-4
500 630 500
GD200-220G/250P-4
630 630 500
GD200-250G/280P-4
630 800 630
GD200-280G/315P-4
700 800 630
GD200-315G/350P-4
800 1000 780
GD200-350G/400P-4
800 1000 780
GD200-400G-4 1000 1250 780
GD200-500G-4 1200 1250 980