Goodrive270 series VFD for fan and pump Basic operation guidelines
-102-
P10.02 multi-step speed 0
P10.03 running time of step 0
P10.04 multi-step speed 1
P10.05 running time of step 1
P10.06 multi-step speed 2
P10.07 running time of step 2
P10.08 multi-step speed 3
P10.09 running time of step 3
P10.10 multi-step speed 4
P10.11 running time of step 4
P10.12 multi-step speed 5
P10.13 running time of step 5
P10.14 multi-step speed 6
P10.15 running time of step 6
P10.16 multi-step speed 7
P10.17 running time of step 7
P10.18 multi-step speed 8
P10.19 running time of step 8
P10.20 multi-step speed 9
P10.21 running time of step 9
P10.22 multi-step speed 10
P10.23 running time of step 10
P10.24 multi-step speed 11
P10.25 running time of step 11
P10.26 multi-step speed 12
P10.27 running time of step 12
P10.28 multi-step speed 13
P10.29 running time of step 13
P10.30 multi-step speed 14
P10.31 running time of step 14
P10.32 multi-step speed 15
P10.33 running time of step 15
BIT0
BIT1
BIT2
BIT3
BIT4
BIT5
BIT6
BIT7
BIT8
BIT9
BIT10
BIT11
BIT12
BIT13
BIT14
BIT15
Terminal function 16
Multi-step speed
terminal 1
Terminal function 17
Multi-step speed
terminal 2
Terminal function 18
Multi-step speed
terminal 3
Terminal function 19
Multi-step speed
terminal 4
P10.34
Acceleration/deceleration time
selection of 07 section of
simple PLC
P00.10 acceleration time 1
P00.12 deceleration time 1
P08.00 acceleration time 2
P08.01 deceleration time 2
P08.02 acceleration time 3
P08.03 deceleration time 3
P08.04 acceleration time 4
P08.15 deceleration time 4
00
01
10
11
BIT0
BIT1
BIT2
BIT3
BIT4
BIT5
BIT6
BIT7
BIT8
BIT9
BIT10
BIT11
BIT12
BIT13
BIT14
BIT15
P00.10 acceleration time 1
P00.12 deceleration time 1
P08.00 acceleration time 2
P08.01 deceleration time 2
P08.02 acceleration time 3
P08.03 deceleration time 3
P08.04 acceleration time 4
P08.15 deceleration time 4
00
01
10
11
P10.35
Acceleration/deceleration time
selection of 815 section of
simple PLC
Multi-step speed
output
Running command
Multi-step speed 0
Multi-step speed 1
Multi-step speed 15
ON
OFF
OFF ON
Terminal function 16
Multi-step speed
terminal 1
Terminal function 17
Multi-step speed
terminal 2
Terminal function 18
Multi-step speed
terminal 3
Terminal function 19
Multi-step speed
terminal 4
OFF ON OFF ON OFF ON
OFF ONOFF ON OFFON OFF ON
OFF ONOFF ONOFF ONOFF ON
Multi-step speed
8 9 10 11 12 13 14 15
ON ONON ON ON ONON ON
OFF ON
Terminal function 16
Multi-step speed
terminal 1
Terminal function 17
Multi-step speed
terminal 2
Terminal function 18
Multi-step speed
terminal 3
Terminal function 19
Multi-step speed
terminal 4
OFF ON OFF ON OFF ON
OFF ONOFF ON OFFON OFF ON
OFF ONOFF ONOFF ONOFF ON
OFF OFF OFF OFF OFF OFF OFF OFF
Multi-step speed
0 1 2 3 4 5 6 7
Frequency-hold
Valid
Invalid
Related parameter list:
Function code
Name
Description
Default
P05.01±P05.06
Digital input function
selection
16: Multi-step speed terminal 1
17: Multi-step speed terminal 2
18: Multi-step speed terminal 3
19: Multi-step speed terminal 4
20: Pause multi-step speed
running
P10.02 Multi-step speed 0 -100.0±100.0% 0.0%
P10.03 Run time of step 0 0.0±6553.5s (min) 0.0s
P10.04 Multi-step speed 1 -100.0±100.0% 0.0%
P10.05 Run time of step 1 0.0±6553.5s (min) 0.0s
P10.06 Multi-step speed 2 -100.0±100.0% 0.0%
P10.07 Run time of step 2 0.0±6553.5s (min) 0.0s
P10.08 Multi-step speed 3 -100.0±100.0% 0.0%