Goodrive270 series VFD for fan and pump Basic operation guidelines
-95-
Function
code
Name Description Default
P07.39
Input terminal status at
present fault
0
P17.12 Digital input terminal status
0
5.5.12 Digital output
The VFD carries two groups of relay output terminals, one open collector Y output terminal and one
high-speed pulse output (HDO) terminal. The function of all the digital output terminals can be
programmed through function codes, of which the high-speed pulse output terminal HDO can also be
set to high-speed pulse output or digital output by function code.
0
1
2
3
4
5
.
.
.
.
29
30
P06.01
P06.03
P06.04
P06.02
T delay
T delay
T delay
T delay
0
1
P06.05 output polarity
selection
(Default value: 0)
(Default value: 0)
(Default value: 1)
(Default value: 5)
P06.00
HDO
input type
0
1
0
1
0
1
delay
0
1
-1
-1
-1
-1
P17.12
Digital input
terminal state
P07.40
Digital output
terminal state
of current fault
FaultË›
Fault
Run
Y BIT0 HDO BIT1
ROI BIT2 RO2 BIT3
P06.05, P17.12, P07.40 display
P06.00
0: Open collector high-
speed pulse output
1: Open collector output
P06.07
P06.09
P06.11
P06.13
Y
RO2
ROI
HDO
Digital switch-off delay
Digital output selection
T delay
T delay
T delay
T delay
delay
P06.06
P06.08
P06.10
P06.12
Digital switch-on delay
The following table lists the function code options. A same output terminal function can be repeatedly
selected.
Setting
Function
Description
0 Invalid
The output terminal does not have any
function.
1 Running
The ON signal is output when there is
frequency output during running.
2 Running forward
The ON signal is output when there is
frequency output during forward running.
3 Running reversely
The ON signal is output when there is
frequency output during reverse running.
4 Jogging
The ON signal is output when there is
frequency output during jogging.
5 VFD in fault
The ON signal is output when a VFD fault
occurred.
6
Frequency level detection FDT1
Refer to the description for P08.32 and P08.33
7
Frequency level detection FDT2
Refer to the description for P08.34 and P08.35
8
Frequency reached
Refer to the description for P08.36