Goodrive270 series VFD for fan and pump Function parameter list
-223-
Function
code
Name Description Default
Modify
P89.31
Accumulative run
time of motor H
0
±65535H 0 ƽ
P89.32
AI/AO measured
temperature
-
20.0±200.0 0 ƽ
P89.33±
P89.35
Reserved
P90 group²PID1 control
Function
code
Name Description Default
Modify
P90.00 Unit selection
0: MPa
1: KPa
2: Pa
3: A
4: V
5: %
6: m/s
7: m/Min
8: m/h
9: m3/s
10: m3/Min
11: m3/h
12: Kg/s
13: Kg/Min
14: Kg/h
15±21: Reserved
0 Ƽ
P90.01
Number of decimal
places
0
±4 3 Ƽ
P90.02
PID1 given max.
value
0.000
±30.000
It is displayed with three decimal places by
default. If P90.01 is changed, the number of
decimal places changes.
1.000 ƻ
P90.03
PID1 reference
upper limit
P90.04
±P90.02 1.000 ƻ
P90.04
PID1 reference
lower limit
0.000
±P90.03 0 ƻ
P90.05
ACC/DEC time of
PID1 reference
value
0.0
±1000.0s 0.0s
P90.06
PID1 reference
0: Keypad (P90.07)
0
ƻ