Goodrive270 series VFD for fan and pump Function parameter list
-189-
Name Description Default
time, and then convert 16
-bit binary number into
hexadecimal number, finally, and then set
correspo
nding function codes.
P00.11 and P00.12;
P08.00 and P08.01;
P08.02 and P08.03;
P08.04 and P08.05.
Setting range: 0x0000±0xFFFF
P10.36 PLC restart mode
0: Restart from the first step, namely if the VFD
stops during running (caused by stop command,
fault or power down), it will run from the first step
after restart.
1: Continue running from the step frequency
when interruption occurred,
namely if the VFD
stops during running (caused by stop command
or fault), it will record the running time of current
step, and enters this step automatically after
restart, then continue running at the frequency
defined by this step in the remaining time.
0 Ƽ
P10.37 Multi-step time unit
0: second; the running time of each step is
counted in seconds
1: minute; the running time of each step is
counted in minutes
0 Ƽ
P11 group²Protection parameters
Name Description Default
P11.00
Protection against
phase loss
±0x111
0: Disable software input phase loss protection.
1: Enable software input phase loss protection.
0: Disable output phase loss protection.
1: Enable output phase loss protection.
0x011 ƻ
P11.01
Frequency drop at
transient power-off
If the bus voltage drops to the sudden frequency
decreasing point due to power failure, the VFD
decreases the running frequency by using the
0 ƻ