Goodrive270 series VFD for fan and pump Function parameter list
-173-
Function
code
Name Description Default
Modify
P07.50
Ramp reference
frequency at
2nd-last fault
0.00Hz
±P00.03 0.00Hz ƽ
P07.51
Output voltage at
2nd-last fault
0
±1200V 0V ƽ
P07.52
Output current at
2nd-last fault
0.0
±6300.0A 0.0A ƽ
P07.53
Bus voltage at
2nd-last fault
0.0
±2000.0V 0.0V ƽ
P07.54
Temperature at
2nd-last fault
-
20.0±120.0°C 0.0°C ƽ
P07.55
Input terminal status
at 2nd-last fault
0x0000
±0xFFFF 0 ƽ
P07.56
Output terminal
status at 2nd-last
fault
0x0000
±0xFFFF 0 ƽ
P08 group²Enhanced functions
Function
code
Name Description Default
Modify
P08.00 ACC time 2
For details, see
P00.11 and P00.12.
The VFD has four groups of ACC/DEC time,
which can be selected by P05. The factory
default ACC/DEC time of the VFD is the first
group.
Setting range: 0.0
±3600.0s
Model
depended
ƻ
P08.01 DEC time 2
Model
depended
ƻ
P08.02 ACC time 3
Model
depended
ƻ
P08.03 DEC time 3
Model
depended
ƻ
P08.04 ACC time 4
Model
depended
ƻ
P08.05 DEC time 4
Model
depended
ƻ
P08.06
Running frequency
of jog
U
sed to define the reference frequency during
jogging.
Setting range: 0.00Hz
±P00.03 (Max. output
frequency)
5.00Hz ƻ
P08.07
ACC time for jogging
ACC time for jogging means the time needed for
the VFD to accelerate from 0Hz to the max.
Model
depended
ƻ

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT GD270-030-4 and is the answer not in the manual?

INVT GD270-030-4 Specifications

General IconGeneral
BrandINVT
ModelGD270-030-4
CategoryWater Pump
LanguageEnglish

Related product manuals