Goodrive270 series VFD for fan and pump Function parameter list
-231-
P93 group²Fire control
Name Description Default
P93.00 Fire mode
When P93.00=0, the fire mode is invalid, the
VFD runs in normal mode and it stops if suffering
a fault. When P93.00 is a non
-zero value and
the
fire signal is activated, the fire mode is valid, and
the VFD runs at the speed specified by P93.01.
If fire mode 1 is selected, the VFD always runs
except it is damaged.
If fire mode 2 is selected, the VFD always runs
except it stops upon the followi
ng faults: OUT1,
OUT2, OUT3, OC1, OC2, OC3, OV1, OV2, OV3,
and SPO.
0 Ƽ
P93.01
Running frequency
±P00.03(Max. output frequency) 50.00Hz ƻ
P93.02
Motor running
0: Run at the default direction.
1: Run at the opposite direction.
0 ƻ
P93.03 Fire mode flag
±1
If the fire mode duration reaches 5 minutes, this
flag is set to 1, and no warranty repair is granted.
0 ƽ
P93.04
Actual month and
date when fire
±12.31 00.00 ƽ
P93.05
Actual time when fire
activated
±23.59 00.00 ƽ
P93.06±
Reserved
P94 group²HVAC
Name Description Default
P94.00
HVAC function
0 Ƽ
P94.01
Sleep method
selection
0: Sleep only through terminals
sed on running frequency
2: Automatic sleep based on deviation
0 ƻ
P00.05±P00.04 (Upper limit frequency)
ƻ