Goodrive270 series VFD for fan and pump Function parameter list
-236-
P95 group²Segmented water pressure
Function
code
Name Description Default
Modify
P95.00 Actual time
00.00
±23.59
Set the clock date and time in group P20.
00.00 ƽ
P95.01
Number of pressure
segments
0
±8
The value 0 indicates this function is disabled.
0 ƻ
P95.02
Start time of T1
Af
ter Tx elapsed, the water pressure changes to
that corresponding to Tx.
The water pressure before T1 is set to 0.
You need to set the end time segment.
P95.01 indicates the number of valid segments.
The setting that is out of the segment range is
invalid.
If the start time of Tx is later than the start time of
T(x+1), T(x+1) automatically changes to Tx.
00.00
ƻ
P95.03
Pressure at T1
0.0%
ƻ
P95.04
Start time of T2
23.00
ƻ
P95.05
Pressure at T2
0.0%
ƻ
P95.06
Start time of T3
23.00
ƻ
P95.07
Pressure at T3
0.0%
ƻ
P95.08
Start time of T4
23.00
ƻ
P95.09
Pressure at T4
0.0%
ƻ
P95.10
Start time of T5
23.00
ƻ
P95.11
Pressure at T5
0.0%
ƻ
P95.12
Start time of T6
23.00
ƻ
P95.13
Pressure at T6
0.0%
ƻ
P95.14
Start time of T7
23.00
ƻ
P95.15
Pressure at T7
0.0%
ƻ
P95.16
Start time of T8
23.59
ƻ
P95.17
Pressure at T8
0.0%
ƻ
P95.18±
P95.19
Reserved
P96 group²HVAC protection
Function
code
Name Description Default
Modify
P96.00
Action upon water
pipe break
0: Normal running
1: Stop
0 ƻ
P96.01
Detection level of
water pipe break
After water pipe break, the VFD running
frequency boosts up to the upper limit or the PID
output upper limit frequency. When it is set to 0,
the water pipe break function is invalid.
Range: 0.0±100.0%
10.0% ƻ
P96.02
Detection time of
water pipe break
Used to check the detection time of water pipe
break.
Range: 0.0±6000.0s
120.0s ƻ