EasyManuals Logo

INVT GD270-030-4 User Manual

INVT GD270-030-4
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #139 background imageLoading...
Page #139 background image
Goodrive270 series VFD for fan and pump Function parameter list
-129-
Function
code
Name Description Default
Modify
selection 1: Valid during the whole procedure
The auto-adjusting function of the VFD can
eliminate the impact on the out
put voltage of the
VFD because of the bus voltage fluctuation.
P00.17
Reserved
P00.18
Function parameter
restore
0: No operation
1: Restore default values
2: Clear fault records
3±6: Reserved
Note: After the selected operation is
performed, the function code is
automatically restored to 0. Restoring the
default values may delete the user password.
Exercise caution when using this function.
0 Ƽ
P01 group²Start and stop control
Function
code
Name Description Default
Modify
P01.00 Start mode
0: Dire
ct start
1: Start after DC braking
2: Speed tracking restart 1 (not supported in SVC
0 for AMs)
Note: In SVC 0, speed tracking cannot be
selected, which indicates P01.00 can be 0 or 1.
0 Ƽ
P01.01
Starting frequency of
direct start
The function code indic
ates the initial frequency
during VFD start. See
P01.02
(Starting frequency
hold time) for detailed information.
Setting range: 0.00±50.00Hz
0.50Hz Ƽ
P01.02
Starting frequency
hold time
Output frequency
fmax
t1
T
F1 set by P01.01
f1
T1 set by P01.02
Setting a prop
er starting frequency can increase
the torque during VFD start. During the hold time
of the starting frequency, the output frequency of
the VFD is the starting frequency. And then, the
0.0s Ƽ

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT GD270-030-4 and is the answer not in the manual?

INVT GD270-030-4 Specifications

General IconGeneral
BrandINVT
ModelGD270-030-4
CategoryWater Pump
LanguageEnglish

Related product manuals