Goodrive270 series VFD for fan and pump Function parameter list
-129-
Name Description Default
selection 1: Valid during the whole procedure
The auto-adjusting function of the VFD can
eliminate the impact on the out
put voltage of the
VFD because of the bus voltage fluctuation.
P00.18
restore
0: No operation
1: Restore default values
2: Clear fault records
3±6: Reserved
Note: After the selected operation is
performed, the function code is
automatically restored to 0. Restoring the
default values may delete the user password.
Exercise caution when using this function.
0 Ƽ
P01 group²Start and stop control
Name Description Default
P01.00 Start mode
ct start
1: Start after DC braking
2: Speed tracking restart 1 (not supported in SVC
0 for AMs)
Note: In SVC 0, speed tracking cannot be
selected, which indicates P01.00 can be 0 or 1.
0 Ƽ
P01.01
direct start
ates the initial frequency
P01.02
(Starting frequency
hold time) for detailed information.
Setting range: 0.00±50.00Hz
0.50Hz Ƽ
P01.02
Starting frequency
hold time
Output frequency
fmax
t1
T
F1 set by P01.01
f1
T1 set by P01.02
er starting frequency can increase
the torque during VFD start. During the hold time
of the starting frequency, the output frequency of
the VFD is the starting frequency. And then, the
0.0s Ƽ