Goodrive270 series VFD for fan and pump Function parameter list
-186-
Function
code
Name Description Default
Modify
P09.15
ACC/DEC time of
PID command
0.0
±1000.0s 0.0s ƻ
P09.16
PID output filter time
0.000±10.000s
0.000s
ƻ
P09.17
Reserved
P09.18
Low frequency
integral time (Ti)
0.00
±10.00s 0.90s ƻ
P09.19
Low frequency
differential time (Td)
0.00
±10.00s 0.00s ƻ
P09.20
Low frequency point
for PID parameter
switching
0.00
±P09.21 5.00Hz ƻ
P09.21
High frequency point
for PID parameter
switching
P09.20
±P00.04 10.00Hz ƻ
P09.22±
P09.28
Reserved
P10 group²Simple PLC and multi-step speed control
Function
code
Name Description Default
Modify
P10.00 Simple PLC mode
0: Stop after running once. The VFD stops
automatically after running for one cycle, and it
c
an be started only after receiving the running
command.
1: Keep running in the final value after running for
one cycle. The VFD keeps the running frequency
and direction of the last section after a single
cycle.
2: Cyclic running. The VFD enters the next c
ycle
after completing one cycle until receiving the stop
command.
0 ƻ
P10.01
Simple PLC memory
selection
0: Without power
-failure memory
1: Memory after power
-off. The PLC memories
its running stage and running frequency before
power-off.
0 ƻ
P10.02
Multi-step speed 0
Frequency setting range for steps
0±15: -100.0±
100.0%. 100.0% corresponds to the max. output
frequency
P00.03.
Running time setting range for steps from
0±15:
0.0 0.0
±6553.5s(min). The time unit is specified
by
P10.37.
0.0%
ƻ
P10.03
Run time of step 0
0.0s (min)
ƻ
P10.04
Multi-step speed 1
0.0%
ƻ
P10.05
Run time of step 1
0.0s (min)
ƻ
P10.06
Multi-step speed 2
0.0%
ƻ
P10.07
Run time of step 2
0.0s (min)
ƻ