Goodrive270 series VFD for fan and pump Function parameter list
-202-
Name Description Default
When M=116%, protection is performed after
motor overload lasts for 1 hour; when M=200%,
protection is performed after motor overload lasts
IRUVHFRQGVDQGZKHQ0SURWHFWLRQLV
performed immediately.
1min
1h
116 % 200 %
Time t
Motor overload multiples
Setting range: 20.0%±120.0%
P12.28
Power display
calibration
±3.00 1.00 ƻ
P12.29
motor 2
0: Display by motor type. In this mode, only
parameters related to the present motor type are
displayed.
1: Display all. In this mode, all the motor
parameters are displayed.
0 ƻ
P12.30
System inertia of
±30.000kgm
2
0.000 ƻ
P12.31±
Reserved
±65535 0 ƻ
P13 group²SM control
Name Description Default
P13.00
SM injected-
decrease ratio
Used to set the reduction rate of the input
reactive current. When the active current of the
synchronous motor increases to some extent, the
input reactive current can be reduced to improve
the power factor of the motor.
±100.0% (of the motor rated
80.0% ƻ
P13.01
Detection mode of
initial pole
-frequency superposition
0 Ƽ