Goodrive270 series VFD for fan and pump Function parameter list
-203-
Name Description Default
P13.02 Pull-in current 1
-in current is the pole position orientation
-in current 1 is valid within the lower
-in current switch-over frequency
threshold. If you need to increase the start
torque, increase t
he value of this parameter
±100.0% (of the motor rated
20.0% ƻ
P13.03 Pull-in current 2
-in current is the pole position orientation
-in current 2 is valid within the lower
-in current switch-over frequency
threshold. You do not need to change the value
in most cases.
±100.0% (of the motor rated
10.0% ƻ
P13.04
Source-current
switchover
±P00.03(Max. output frequency) 10.00Hz ƻ
P13.06
High-frequency
superposition
voltage
Used to set the pulse current threshold when the
initial magnetic pole position is detected in the
pulse mode, The value is a percentage in relative
to the rated current of the motor.
±300.0% (of the motor rated
100.0% Ƽ
ƻ
P13.09 Control parameter 2
Used to set the frequency threshold for enabling
the counter
-electromotive force phase-locked
VC 0. When the running frequency is
lower than the value of the function code, the
phase
-locked loop is disabled; and when the
running frequency is higher than that, the
phase
-locked loop is enabled.
50.00 ƻ
ƻ
Used to adjust the responsiveness of
ƻ