Goodrive270 series VFD for fan and pump    Function parameter list 
-133- 
Name  Description  Default 
does not run and it keeps the protection state 
until the running command is canceled and 
enabled again.
 
1: The terminal running command is valid at 
power
-on
. If the running command is considered 
as valid during power
-on, the VFD is started 
automatically after the initialization.
 
Note: Exercise caution before using this function. 
Otherwise, serious result may follow. 
P01.19 
Action selected 
when running 
frequency less than 
frequency lower limit 
(valid when 
greater than 0) 
etermines the run status of the VFD when the 
set frequency is lower than the lower
-limit one. 
 the frequency lower limit 
 
 
The VFD coasts to stop when the set frequency 
is lower than the lower
-limit one. If the set 
frequency exceeds the lower limit one again and 
it lasts for the time set by 
P01.20, the VFD 
resumes the running state automatically. 
0  Ƽ 
P01.20 
Wake-up-from- 
sleep delay 
-up-from-sleep delay time. 
When the running frequency of the VFD is lower 
than the lower limit, the VFD becomes standby.
 
When the set frequency exceeds the lower limit 
one again and it lasts for the t
ime set by P01.20
, 
the VFD runs automatically.
 
Sleep
Run
Set frequency curve:
Running frequency curve:
t1 < P01.20, the VFD does not run
t0=P01.34, sleep delay
Run
t2
t1
t0
Frequency lower
limit f0
Frequency f
Time t
Coast to
stop
t1+t2 ıP01.20, the VFD runs
 
±3600.0s (Valid only when 
0.0s  ƻ 
P01.21 
Power-off restart 
ndicates whether the VFD automatically runs 
0  ƻ