EasyManua.ls Logo

INVT GD270-030-4 - Page 145

INVT GD270-030-4
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Goodrive270 series VFD for fan and pump Function parameter list
-135-
Function
code
Name Description Default
Modify
P01.31
Hold time of
short-
circuit braking
for stop
stop (
P01.09), set P01.31 to a non-zero value to
enter short
-
circuit braking for stop, and then carry
out DC braking in the t
ime set by P01.12. (See
descriptions for
P01.09±P01.12.)
P01.29
setting range: 0.0±150.0% (VFD)
P01.30
setting range: 0.0±50.00s
P01.31 setting range: 0.0±50.00s
0.00s ƻ
P01.32
Pre-
exciting time for
jogging
0
±10.000s 0.300s ƻ
P01.33
Starting frequency of
braking for stop in
jogging
0
±P00.03 0.00Hz ƻ
P01.34
Sleep delay
0±3600.0s
0.0s
ƻ
P01.35
Speed tracking
method
Speed tracking method
0: From stop frequency
1: From low frequency
2: From max. frequency (P00.03)
0 ƻ
P01.36
Quick/slo
w selection
for speed tracking
1
±100 15 ƻ
P01.37
Speed tracking
current
30%
±200% (motor) 100% ƻ
P01.38
Demagnetization
time for speed
tracking
0.0
±10.0s
Model
depended
ƻ
P01.39
Advanced control for
speed tracking
0x000
±0x111
LED ones place: Current givi
ng mode in vector
control
0: 120% of current is given during startup, which
is switched to the given value based on P01.35
1: The current is given based on P01.35
LED ones place: PWM mode selection
0: 2PH modulation mode
1: Based on P08.40
LED hundreds pla
ce: Search direction for speed
tracking
0: Allow both forward and reverse search
1: Disallow reverse search
0x110 ƻ

Table of Contents