Goodrive270 series VFD for fan and pump Function parameter list
-141-
Function
code
Name Description Default
Modify
P03.13
Torque reference
filter time
0.000
±10.000s 0.010s ƻ
P03.14
Setting source of
forward rotation
upper-limit
frequency in torque
control
0: Keypad (
P03.16)
1: AI1
2: AI2
3: AI3
4: Pulse frequency HDIA
5: Multi
-step setting
6: Modbus communication
7:
PROFIBUS/CANopen/DeviceNet
communication
8: Ethernet communication
9: Reserved
10: EtherCAT/PROFINET communication
11: Programmable expansio
n card
12
±17: Reserved
18: Keypad (for small power models)
Note: For setting
sources 1±5, 100%
corresponds to the max. frequency.
0 ƻ
P03.15
Setting source of
reverse rotation
upper-limit
frequency in torque
control
0: Keypad (
P03.17)
1: AI1
2: AI2
3: AI3
4: Pulse frequency HDIA
5: Multi
-step setting
6: Modbus communication
7:
PROFIBUS/CANopen/DeviceNet
co
mmunication
8: Ethernet communication
9: Reserved
10: EtherCAT/PROFINET communication
11: Programmable expansion card
12
±17: Reserved
18: Keypad (for small power models)
Note: For setting
sources 1±5, 100%
corresponds to the max. frequency.
0 ƻ
P03.16
Forward rotation
upper-limit
Used to set the frequency upper limits. 100%
corresponds to the max. frequency. P03.16 sets
50.00Hz ƻ