Goodrive270 series VFD for fan and pump Function parameter list
-175-
Name Description Default
P08.21
of ACC/DEC time
Note: Valid only for straight-line ACC/DEC
0 Ƽ
P08.22
Output torque
ue current
0 ƻ
P08.23
Number of decimal
0 ƻ
P08.24
Number of decimal
points of linear
speed
0 ƻ
ƻ
P08.26
Designated counting
value
±P08.25 0 ƻ
ƻ
P08.28
Auto fault reset
count
Auto fault reset count: When the VFD uses
automatic fault reset, it is used to set the number
of automatic fault reset times. When the number
of continuous reset times exceeds the value, the
VFD reports a fault and stops.
Auto fault reset interval: Time interval from when
a fault occurred to when automatic fault reset
takes effect.
If no fault occurred within 600s
after the VFD starts, the number of automatic
fault reset times is cleared.
setting range: 0±10
P08.29 setting range: 0.1±3600.0s
0 ƻ
P08.29
Auto fault reset
interval
1.0s ƻ
P08.30
ratio in drop control
The output frequency of the VFD changes as the
load changes. The function code is mainly used
to balance the power when several motors drive
a same load.
Setting range: 0.00±50.00Hz
0.00Hz ƻ
P08.31
Channel for
switching between
±0x14
Ones place: Switchover channel
0x00 Ƽ