Goodrive270 series VFD for fan and pump    Troubleshooting 
-241- 
Fault 
Fault type  Possible cause  Solution 
OUt3 
Inverter unit 
W-phase protection 
Drive wires connected 
poorly. 
To -ground short circuit 
interference surrounding the 
peripheral device. 
OV1 
Overvoltage during 
DEC time too short. 
Input voltage exception. 
Large energy feedback. 
No braking components. 
Energy-consumption 
braking is not enabled. 
Check the input power. 
Check whether load DEC time is 
too short or the motor starts 
during rotating. 
Install dynamic braking 
components. 
Check the setting of related 
OV2 
Overvoltage during 
OV3 
Overvoltage during 
constant speed 
running 
OC1 
Overcurrent during 
ACC 
ACC/DEC too fast. 
Grid voltage too low. 
VFD power too small. 
Load transient or 
exception occurred. 
To -ground short circuit or 
output phase loss 
occurred. 
Strong external 
interference sources. 
The overcurrent stall 
protection is not enabled. 
Increase ACC/DEC time. 
Check the input power. 
Select a VFD with larger power. 
Check whether the load is short 
circuited (to-ground short circuit 
or line-to-line short circuit) or the 
rotation is not smooth. 
Check the output wiring. 
Check if there is strong 
interference. 
Check the setting of related 
OC2 
Overcurrent during 
deceleration 
OC3 
Overcurrent during 
constant speed 
running 
UV 
Bus undervoltage 
fault 
Grid voltage too low. 
The overvoltage stall 
protection is not enabled. 
Check the grid input power. 
Check the setting of related 
OL1  Motor overload 
Grid voltage too low. 
Motor rated current set 
incorrectly. 
The motor stall occurs or 
the load transient is too 
Check the grid voltage. 
Reset the rated current of the 
motor. 
Check the load and adjust the 
torque boost quantity. 
OL2  VFD overload 
ACC too fast. 
The motor in rotating is 
restarted. 
Grid voltage too low. 
Increase ACC time. 
Avoid restart after stop. 
Check the grid voltage. 
Select a VFD with larger power.