Goodrive270 series VFD for fan and pump Troubleshooting
-246-
Fault
Fault type Possible cause Solution
occurs at next power-on;
Check whether the insertion port
is damaged, if yes, replace the
insertion port after power-off.
C2-Er
Communication
timeout occurred to
the expansion card
in card slot 2
There is no data
transmission in interfaces
of card slot 2.
Check whether the expansion
card at this slot is supported.
Stabilize the expansion card
interfaces after power-off, and
confirm whether a fault still
occurs at next power-on;
Check whether the insertion port
is damaged, if yes, replace the
insertion port after power-off.
E-DP
PROFIBUS card
communication
timeout fault
There is no data
transmission between the
communication card and
the host computer (or
Check whether the
communication card wiring is
loose or dropped.
E-NET
Ethernet card
communication
timeout fault
There is no data
transmission between the
communication card and
Check whether the
communication card wiring is
loose or dropped.
E-CAN
CANopen card
communication
timeout fault
There is no data
transmission between the
communication card and
the host computer (or
Check whether the
communication card wiring is
loose or dropped.
E-PN
PROFINET card
communication
timeout fault
There is no data
transmission between the
communication card and
the host computer (or
Check whether the
communication card wiring is
loose or dropped.
E-CAT
EtherCAT card
communication
timeout fault
There is no data
transmission between the
communication card and
the host computer (or
Check whether the
communication card wiring is
loose or dropped.