EasyManua.ls Logo

INVT GD270-030-4 - Page 44

INVT GD270-030-4
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Goodrive270 series VFD for fan and pump Installation guidelines
-34-
Terminal
Description
jumpers J7 and J6.
Error: ±0.5% when output is 5V at 25°C
RO1A
RO1 output; RO1A: NO; RO1B: NC; RO1C: common
Contact capacity: 3A/AC250V, 1A/DC30V
RO1B
RO1C
COM
+24V common terminal
Y1
Switch capacity: 50mA/30V
Output frequency range: 0±1kHz
Y1 and S4 share the output terminal. The selection is made through J10.
485+
RS485 communication port, RS485 differential signal port and standard RS485
communication port must use twisted shielded pairs; the 120ohm terminal
matching resistor for RS485 communication is connected through jumper J8.
485-
PE
Grounding terminal
PW
Used to provide input digital working power from the external to the internal
Voltage range: 12±30V
24V
User power supply provided by the VFD. Max. output current: 200mA
COM
+24V common terminal
S1 Digital input 1
1. ,QWHUQDOLPSHGDQFHNȍ
2. 12±24V voltage input is acceptable
3. Bi-direction input terminal, supporting both NPN and PNP
4. Max. input frequency: 1kHz
5. All are programmable digital input terminals, the functions of
which can be set through function codes
6. S4 and Y1 share the output terminal. The selection is made
through J10.
S2 Digital input 2
S3 Digital input 3
S4 Digital input 4
HDIA
In addition to digital input functions, the terminal can also act as a high frequency
pulse input channel.
Max. input frequency: 50kHz
Duty ratio: 30%±70%