Goodrive270 series VFD for fan and pump Basic operation guidelines
-49-
Function
code
Name Description Default
autotuning 1 is used in cases where the motor cannot be
disconnected from load.
3: Static autotuning 2 (partial autotuning); when the
present motor is motor 1, only P02.06, P02.07, and
P02.08 are autotuned; when the present motor is motor
2, only P12.06, P12.07, and P12.08 are autotuned.
4: Rotary autotuning 2, which is similar to rotary
autotuning 1 but only valid for AMs.
5: Static autotuning 3 (partial autotuning), which is valid
only for AMs.
P02.00 Type of motor 1
0: Asynchronous motor (AM)
1: Synchronous motor (SM)
0
P03.00
Speed-loop
proportional
gain 1
0±200.0 20.0
P03.01
Speed-loop
integral time 1
0.000±10.000s 0.200s
P03.02
Low-point
frequency for
switching
0.00Hz±P03.05 5.00Hz
P03.03
Speed-loop
proportional
gain 2
0±200.0 20.0
P03.04
Speed-loop
integral time 2
0.000±10.000s 0.200s
P03.05
High-point
frequency for
switching
P03.02±P00.03 (Max. output frequency) 10.00Hz
P03.06
Speed-loop
output filter
0±8 (corresponding to 0±2
8
/10ms) 0
P03.07
Electromotive
slip
compensation
coefficient of
vector control
50%±200% 100%
P03.08
Braking slip
compensation
50%±200% 100%