Goodrive270 series VFD for fan and pump Basic operation guidelines
-70-
Function
code
Name Description Default
P02.06
Stator resistance of AM
1
0.001±ȍ
Model
depended
P02.07 Rotor resistance of AM 1
0.001±ȍ
Model
depended
P02.08
Leakage inductance of
AM 1
0.1±6553.5mH
Model
depended
P02.09
Mutual inductanc
e of AM
1
0.1±6553.5mH
Model
depended
P02.10 No-load current of AM 1 0.1±6553.5A
Model
depended
P02.15 Rated power of SM 1 0.1±3000.0kW
Model
depended
P02.16 Rated frequency of SM 1
0.01Hz±P00.03(Max. output frequency) 50.00Hz
P02.17
Number of pole pairs of
SM 1
1±50 2
P02.18 Rated voltage of SM 1 0±1200V
Model
depended
P02.19 Rated current of SM 1 0.8±6000.0A
Model
depended
P02.20
Stator resistance of SM
1
0.001±ȍ
Model
depended
P02.21
Direct-
axis inductance of
SM 1
0.01±655.35mH
Model
depended
P02.22
Quadrature-axis
inductance of SM 1
0.01±655.35mH
Model
depended
P02.23 Counter-
emf constant of
SM 1
0±10000 300
P05.01±
P05.06
Function selection of
multifunction
digital input
terminals (S1±S4, and
HDIA)
35: Switch from motor 1 to motor 2
P08.31
Switching between
motor 1 and motor 2
0x00±0x14
Ones place: Switchover channel
0: Terminal
1: Modbus communication
2: PROFIBUS/CANopen/DeviceNet
communication
00