Goodrive270 series VFD for fan and pump Basic operation guidelines
-74-
Function
Name Description Default
Starting frequency hold time 0.0±50.0s 0.0s
Braking current before start
DC braking time before start 0.00±50.00s 0.00s
P01.05
ACC/DEC mode
0: Linear
1: S curve
Note: If mode 1 is selected, set P01.06
,
P01.07, P01.27 and P01.28
0
P01.08
Stop mode
0: Decelerate to stop
1: Coast to stop
0
P01.09
Starting frequency of DC
0.00Hz±P00.03(Max. output frequency) 0.00Hz
P01.10
Wait time before DC braking
for stop
0.00±50.00s 0.00s
DC braking current for stop
DC braking time for stop 0.00±50.00s 0.00s
P01.13
FWD/REV running
0.0±3600.0s 0.0s
P01.14
FWD/REV running switching
mode
0: Switch at zero frequency
1: Switch at the starting frequency
2: Switch after the speed reaches the stop
speed with a delay
0
P01.16
Stop speed detection mode
0: Detect by t
he set speed (unique in space
voltage vector control mode)
1: Detect by the feedback speed
1
P01.18
Terminal-based running
command protection at
power-on
0: The terminal running command is invalid
at power-on
1: The terminal runn
ing command is valid at
power-on
0
P01.19
Action selected when
running frequency less than
frequency lower limit (valid
when frequency lower limit
0: Run at the frequency lower limit
1: Stop
2: Sleep
0
0.0±3600.0s (valid when P01.19 is 2)
P01.21
Power-off restart selection
0: Disable
0
P01.22
Wait time for restart after
0.0±3600.0s (valid when P01.21 is 1) 1.0s