Goodrive30 Series VFD Function parameter list
-87-
Function
code
Name
Description
Default
Modify
P08.38
Energy
consumptio
n braking
threshold
voltage
The function code is used to set the starting bus
voltage of energy consumption braking. Adjust
this value properly to achieve effective braking
for the load. The default value varies depending
on the voltage class.
220V
voltage:
380.0V
380V
voltage:
700.0V
P08.39
Running
mode of
cooling fan
0: Common running mode
1: The fan keeps running after power-on
0
P08.40
PWM
selection
0x000x21
Ones place: PWM mode selection
0: PWM mode 1, 3PH modulation and 2PH
modulation
1: PWM mode 2, 3PH modulation
Tens place: low-speed carrier frequency limit
mode
0: Low-speed carrier frequency limit mode 1, the
carrier frequency will limit to 2k if it exceeds 2k at
low speed
1: Low-speed carrier frequency limit mode 2, the
carrier frequency will limit to 4k if it exceeds 4k at
low speed
2: No limit
01
P08.41
Overmodul
ation
Ones place:
0: Disable overmodulation
1: Enable overmodulation
Tens place
0: Mild overmodulation; in zone 1
1: Deepened overmodulation, in zone 2
01
P08.42
Data control
set through
keypad
0x0000x1223
Ones place: Frequency enabling selection
0: Both / keys and analog potentiometer
adjustments are valid
1: Only / keys adjustment is valid
2: Only analog potentiometer adjustments is
valid
3: Neither / keys nor digital potentiometer
0x0000

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive30 VFD Series and is the answer not in the manual?

INVT Goodrive30 VFD Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive30 VFD Series
CategoryInverter
LanguageEnglish

Related product manuals