Goodrive30 Series VFD Function parameter list
-87-
Energy
consumptio
n braking
threshold
voltage
The function code is used to set the starting bus
voltage of energy consumption braking. Adjust
this value properly to achieve effective braking
for the load. The default value varies depending
on the voltage class.
Running
mode of
cooling fan
0: Common running mode
1: The fan keeps running after power-on
0x00–0x21
Ones place: PWM mode selection
0: PWM mode 1, 3PH modulation and 2PH
modulation
1: PWM mode 2, 3PH modulation
Tens place: low-speed carrier frequency limit
mode
0: Low-speed carrier frequency limit mode 1, the
carrier frequency will limit to 2k if it exceeds 2k at
low speed
1: Low-speed carrier frequency limit mode 2, the
carrier frequency will limit to 4k if it exceeds 4k at
low speed
2: No limit
Ones place:
0: Disable overmodulation
1: Enable overmodulation
Tens place
0: Mild overmodulation; in zone 1
1: Deepened overmodulation, in zone 2
Data control
set through
keypad
0x000–0x1223
Ones place: Frequency enabling selection
0: Both ∧/∨ keys and analog potentiometer
adjustments are valid
1: Only ∧/∨ keys adjustment is valid
2: Only analog potentiometer adjustments is
valid
3: Neither ∧/∨ keys nor digital potentiometer