10 Technical data
102 2011-07-01/00561073 [SCR Power Controller TYA202]
10.3 Analog inputs (only master)
10.4 Analog output (actual value output, only master)
10.4.1Display and measuring accuracy
All specifications refer to the controller nominal data.
10.5 Binary inputs
10.6 Binary output (fault signal output, only master)
Current 0 (4) … 20mA Ri = 50 W
Voltage 0 (2) … 10V Ri = 25 kW
0 (1) … 5V Ri = 25 kW
Analog output
Switched off as standard.
Imax = 20 mA for standard signal, voltage: 0 … 10V , 2 … 10V,
0…5V to 1…5V.
Burden max. 500 W for standard signal, current: 0 … 20mA to
4 … 20mA
Various internal measuring variables such as load current, load volt-
age or power can be output depending on the device type.
Supply voltage: ±2.5% Load current: ±1% Load voltage: ±1% Power: ±2%
Analog input
voltage/current: ±
1%
Analog output
voltage/current: ±1%
Load resistance: ±
2%
(for resistive load)
12
11
+
–
Binary input 1 for connection to potential-free contact
Binary input 2
Relay (changeover contact)
without contact suppression
150000 switching actions at a contact rating of 3 A/230 V 50 Hz (resistive
load)
Optocoupler output I
Cmax
= 2 mA, U
CEOmax
= 32 V