2011-07-01/00561073 [SCR Power Controller TYA202] 63
5 Configuration
5.2 Configuration example
Requirements Controller load voltage 400V
Load voltage 230V (star connection)
3 heating elements (3 elements with 1kW each connected in parallel)
Load current: 9000W/(3x230V)= 13A
Temperature coefficient TC = 1
Operating mode: Phase-angle control
Cascade control: U
2
Base load: 0%; maximum output level 100%
Default set point value via input signal of 0 ... 20mA.
These requirements are sufficient for the following power controllers:
Device type 70.9062/8-01-020-100
-400-252
Attention:
- make sure that the rotating
electric field is right handed!
- only possible in burst firing mode
- SCR load voltage =U
L
Fuse for control
electronics 2A
Fusing to protect the
power section cabling
0(4)...20mA
Setpoint lnput:
U = phase-phase voltage
U = phase-neutral voltage
U = voltage on thyristor power unit
L
N
Thy
P = total controlled power
I = current in phase conductor
I = current in thyristor power unit
tot
L
Thy
ohmic load star
connection
U1U2
N/L2
L1
V
13
14
15
1211
1089
7
6
5
42
3
1
8
1
U1U2
Semiconductor-
fuse
Semiconductor-
fuse
N/L2
L1
V
13
14
15
1211
1089
7
6
5
42
3
1
8
1
S
Relay
Ö
P
-
+
Patchcable
TYA 202
E
Optocoupler
C
U= U
Thy L
I=
Thy
P
tot
3 · U
N
=
P
tot
3 U
L
·
I=
Thy
I
L
I
Thy
L1
N
L2
L3 PE
U
L
U
N
I
L