5 Configuration
52 2011-07-01/00561073 [SCR Power Controller TYA202]
Resistance limita-
tion
Note: Resistance limitation is only possible for controllers
with current and voltage measurement in which the cas-
cade control P (code 001 in the
order code) is integrated.
no No resistance limitation
yes The load resistance is monitored to ensure that the set resis-
tance limit is not exceeded.
In phase angle control mode, limitation is made via the phase
angle a.
In burst-firing mode, limitation is made via the ON/OFF ratio of
the sine waves.
v Chapter 6.6 „Resistance limitation (R control)“
Resistance limit
value
0...999.99 If the load resistance exceeds this value, it is limited by phase
angle control or limitation of the switched sine waves.
Dual energy man-
agement
switched off This parameter only appears for the following settings:
Cycle time: Fixed (500ms),
v Chapter 5.1.2 „Power controller“ ➔ Cycle time
Operating mode: Burst-firing operation
This allows 2 devices
1
to be set in such a way that they do not
consume energy from the power supply at the same time for
small output levels.
This avoids current peaks.
v Chapter 6.4 „Dual energy management“
Device1
Device2
1. The Master/Slave connection, type 70.9062, is treated as "one“ device.
Value/settings Description
k/ bold = factory setting