EasyManua.ls Logo

JUMO TYA 202 - Binary Inputs; Ext. Current Limiting; External Current, Limit Value; Key Lock

JUMO TYA 202
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 Configuration
58 2011-07-01/00561073 [SCR Power Controller TYA202]
5.1.6 Binary inputs
2 binary inputs are provided, and an additional binary input for firing-pulse in-
hibit to which a potential-free contact can be connected.
The following functions can be triggered with binary input 1 and 2:
h Use the key to change to the Config level
Binary inputs
Value/settings Description
Ext. current limiting
This function can only be set with the following
presettings:
Possibility 1:
Controller
Operating mode Phase angle control and
controller
Current limitation Yes
Possibility 2:
Controller
Operating mode Pulse groups
Controller
Soft start yes
Controller
Current limiting yes
If, for example, "Binary input 1“ is set here, the current limit
value set under "Controller
Current limit value“ is overwrit-
ten when the binary input is closed and the "External current
limit value“ (further down in the table) becomes effective.
switched off No ext. current limiting
Binary input 1
External current limiting is controlled by binary input1
Binary input 2
External current limiting is controlled by binary input2
Ext. binary input1
External current limiting is controlled via an interface
Ext. binary input2
External current limiting is controlled via an interface
External current,
limit value
10% ... max. load
current +10% of the
device type
This parameter only appears if a binary input is set for external
current limitation.
The max. load current varies according to the device type.
For 20A power controllers it is possible to set 2 ... 22A.
Chapter 1.3 „Order specifications“
Key lock switched off No key lock
Binary input 1
The key lock is controlled by binary input1
Binary input 2
The key lock is controlled by binary input2
Ext. binary input1
The key lock is controlled via an interface
Ext. binary input2
The key lock is controlled via an interface
External display
lighting
switched off
No external switch-off, i.e. the background lighting
behaves as configured in Chapter 5.1.1
Binary input 1
Switch-off is controlled by binary input1
Binary input 2
Switch-off is controlled by binary input2
Ext. binary input1
Switch-off is controlled via an interface
Ext. binary input2
Switch-off is controlled via an interface
Control direction,
inhibit input
The firing-pulse inhibit can be triggered when the change-over
contact is closed or open.
v Chapter 3.3 „Connection diagram“
Open, load ON
Open, load OFF
k/ bold = factory setting
7
8
3,3V
5k
W

Table of Contents