4 Operation
46 2011-07-01/00561073 [SCR Power Controller TYA202]
This function is not factory configured.
This window only appears after the following setting in
the configuration level:
h Use the key to change to the configuration level
h Monitoring
Teach-in type load monit. Manual
setting
h Press the key
Now the function "Manual teach-in" has been
configured.
h Change to the operator level
Monitoring
Load monit. teach-in
h Press the key
Now a mask appears asking if the status is to be
applied now. If the answer to this is yes,
h Press the key and the current load status will be
applied as the OK status.
Any change in the load (load error) will be evaluated by
the device on the basis of this status.
Overcurrent
k / Bold = factory setting