Parts and Tools Required for Connecng an EX Series Switch to Earth Ground
Before you begin connecng an EX Series switch to earth ground, ensure you have the parts and tools
required for your switch.
Table 58 on page 165 lists the earthing terminal locaon, grounding cable and lug specicaons, and
parts needed for connecng an EX Series switch to earth ground.
Table 58: Parts Required for Connecng an EX Series Switch to Earth Ground
Switch Earthing
Terminal
Locaon
Grounding
Cable
Requirements
Grounding Lug
Specicaons
Screws and
Washers
Addional
Informaon
EX2200 Rear panel of
the chassis
14 AWG
(2 mm²),
minimum 90° C
wire, or as
permied by
the local code
Panduit
LCC10-14BWL or
equivalent—
not provided
Two
10-32 x .25 i
n. screws
with #10
split-lock
washer—
not provided
Two #10 at
washers—
not provided
EX2300-C Rear panel of
the chassis
14 AWG
(2 mm²),
minimum 90° C
wire, or as
permied by
the local code
Panduit
LCC10-14AW-L or
equivalent—
not provided
Two
10-32 x .25 i
n. screws
with #10
split-lock
washer—
not provided
Two #10 at
washers—
not provided
165