Table 58: Parts Required for Connecng an EX Series Switch to Earth Ground
(Connued)
Switch Earthing
Terminal
Locaon
Grounding
Cable
Requirements
Grounding Lug
Specicaons
Screws and
Washers
Addional
Informaon
EX3200
and
EX3300
Rear panel of
the chassis
14 AWG
(2 mm²),
minimum 90° C
wire, or as
permied by
the local code
Panduit
LCC10-14BWL or
equivalent—
not provided
Two
10-32 x .25 i
n. screws
with #10
split-lock
washer—
not provided
Two #10 at
washers—
not provided
For EX3200
Switches, see
"Special Instrucons
to Follow Before
Connecng Earth
Ground to an EX
Series Switch" on
page 171.
EX3400 Rear panel of
the chassis
14-10 AWG
STR (2.5-6
mm²), minimum
90° C wire, or
as permied by
the local code
Panduit
LCD10-10A-L or
equivalent—
not provided
Two
10-32 x .25 i
n. screws
with #10
split-lock
washer—
not provided
Two #10 at
washers—
not provided
EX4200 Le side of
the chassis
14 AWG
(2 mm²),
minimum 90° C
wire, or as
permied by
the local code
Panduit
LCC10-14BWL or
equivalent—
not provided
Two 10-32
x .25 in.
screws with
#10 split-
lock washer
not provided
Two #10 at
washers—
not provided
See "Special
Instrucons to
Follow Before
Connecng Earth
Ground to an EX
Series Switch" on
page 171.
167