Table 66: show chassis temperature-thresholds Output Fields
Field Name Field Descripon
Item Chassis component. You can congure the threshold informaon
for components such as the chassis, the Roung Engines, and FPC
for each slot in each FRU to display in the output. By default,
informaon is displayed only for the chassis and the Roung
Engines.
Fan speed Temperature thresholds, in degrees Celsius, for the fans to operate
at normal and at high speed.
NormalThe temperature threshold at which the fans operate
at normal speed and when all the fans are present and
funconing normally.
HighThe temperature threshold at which the fans operate at
high speed or when a fan has failed or is missing.
NOTE: An alarm is triggered when the temperature exceeds the
threshold sengs for a yellow, amber, or red alarm.
Yellow or amber alarm Temperature threshold, in degrees Celsius, that triggers a yellow or
amber alarm.
NormalThe temperature threshold that must be exceeded on
the device to trigger a yellow or amber alarm when the fans are
running at full speed.
Bad fanThe temperature threshold that must be exceeded on
the device to trigger a yellow or amber alarm when one or more
fans have failed or are missing.
Red alarm Temperature threshold, in degrees Celsius, that triggers a red alarm.
NormalThe temperature threshold that must be exceeded on
the device to trigger a red alarm when the fans are running at
full speed.
Bad fanThe temperature threshold that must be exceeded on
the device to trigger a red alarm when one or more fans have
failed or are missing.