Table 65: show chassis environment Output Fields
(Connued)
Field Name Field Descripon
Status Status of the specied chassis component. For example, if Class is Fans, the fan status
can be:
• OK: The fans are operaonal.
• Testing: The fans are being tested during inial power-on.
• Failed: The fans have failed or the fans are not spinning.
• Absent: The fan tray is not installed.
Measurement Depends on the Class. For example, if Class is Temp, indicates the temperature in degrees
Celsius (°C) and degrees Fahrenheit (°F). If the Class is Fans, indicates actual fan RPM.
2. Issue the command show chassis temperature-thresholds . This command displays the chassis
temperature threshold seî¾®ngs. Following is a sample output on an EX9208 switch. The output is
similar on other EX Series switches.
show chassis temperature-thresholds (EX9208 Switch)
user@ host> show chassis temperature-thresholds
Fan speed Yellow alarm Red alarm Fire Shutdown
(degrees C) (degrees C) (degrees C) (degrees C)
Item Normal High Normal Bad fan Normal Bad fan Normal
Chassis default 48 54 65 55 80 65 100
Routing Engine 0 70 80 95 95 110 110 112
FPC 3 55 60 75 65 105 80 110
FPC 5 55 60 75 65 90 80 95
Table 66 on page 312 lists the output elds for the show chassis temperature-thresholds command. The
table lists output elds in the approximate order in which they appear.