Configuration and Programming
February 2012 3-8 P/N 06-237058-001
FOOTNOTES (Figure 3-10):
1 SLC Devices. Purpose: To prevent initiating and trouble signals from selected SmartOne
automatic detectors and monitor modules from being processed and acted upon by the ARIES
NETLink control unit. Also to prevent selected SmartOne control and relay modules from
carrying out activation instructions issued by the ARIES NETLink control unit. Note: An SLC
device can only be isolated if it is not in either a trouble or alarm condition.
2 RRM and Output Groups. Purpose: To prevent selected RRM or Output (AO and ASM) group
SLC based output devices from carrying out activation instructions issued by the ARIES NETLink
control unit.