Configuration and Programming
P/N 06-237058-001 3-13 February 2012
FOOTNOTES (Figure 3-14):
1 Isolated Devices. Purpose: To view the list of isolated devices and output circuits.
2 All System Events. List the Entire Contents of the System Event Log. Purpose: To view the
history of system events.
3 Range of Events. List the Contents of the System Event Log by Dates. Purpose: To view the
history of system events by selected dates.
4 SLC Test Results. List the Most Recent Test Results for the Initiating Devices on the SLC.
Purpose: To view the most-recent test results for the initiating devices on the SLC. These tests
confirm the abilities of the initiating devices to create and transmit alarm signals that can be
properly interpreted and processed by the ARIES NETLink control unit.
5 Walk Test Results. List Most Recent WalkTest Results for the Initiating Devices on the SLC.
Purpose: To view the most-recent walk-test results for the initiating devices on the SLC.
6 Device Readings. List a Range of Automatic Detector Sensitivity Settings. Purpose: To view
the pre-alarm and alarm thresholds for a range of automatic detectors and to view the fire
signatures being currently measured by the detectors. This procedure fulfills the intent of NFPA
72 as a test to ensure that each smoke detector is within its listed and marked sensitivity range.
7 Active Events. Purpose: To view the list of active events by event type. Use this option to view
lower-level events such as trouble events whose display is suppressed by the concurrent
occurrence of higher-level events.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde Fire Systems ARIES NETLink and is the answer not in the manual?

Kidde Fire Systems ARIES NETLink Specifications

General IconGeneral
BrandKidde Fire Systems
ModelARIES NETLink
CategoryControl Unit
LanguageEnglish

Related product manuals