Configuration and Programming
February 2012 3-52 P/N 06-237058-001
FOOTNOTES (Figure 3-40):
10 SLC Resistance. Measure SLC Resistance. Purpose: To measure the SLC line resistance.
Note: The SLC line resistance cannot be measured for CLASS-B SLCs with T-Tapping.
11 Find Dup Address. How to Find a Duplicate Address.
Purpose: To clear the trouble message that appears when two SLC devices have been accidentally
assigned the same address. The location of the affected SLC devices can be found by instructing the
control unit to modify the doubly addressed devices LED pulse pattern.
Note: Only one address can be selected at a time if more than one double-address trouble exists.