Troubleshooting
P/N 06-237058-001 7-27 February 2012
ATMAddr Test Lamps Input Fault
On
An open circuit in wiring from the
ATML's Lamp Test" input terminal to
the associated annunciator's lamp-test.
• Refer to ATM Installation Manual, P/N
06-236179-002.
• Look for discontinuity in wiring to
lamp-test switch
• Check for missing 10k end-of-line
resistor
Table 7-7. ATM Events
ATM Events
Error Message Probable Cause Corrective Action